# UPS with SNMP - tested on Riello # # battery status and ups load # [value:minutes_remaining] oid = .1.3.6.1.2.1.33.1.2.3.0 warning = minutes_remaining < 7 critical = minutes_remaining < 5 name = Minutes remaining units = min [value:battery_status] oid = .1.3.6.1.2.1.33.1.2.1.0 warning = battery_status != 2 name = Battery status [value:load] oid = .1.3.6.1.2.1.33.1.4.4.1.5.1 units = % warning = (load > 85) critical = (load > 90) name = Output load